fire code, O. Reg. 213/07

Section 9.6.2.16

Cite as fire code, O. Reg. 213/07, s. 9.6.2.16 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) Buildings where the vertical distance between the floor of the top storey and grade exceeds 18 m shall have smoke control measures in accordance with Article 3.2.6.2. of the 1990 Building Code. (2) Buildings are deemed to be in compliance with Sentence (1) where (a) all dwelling units have access to an exterior balcony, (b) the length of public corridors does not exceed 30 m between exits, (c) public corridors on each floor area are equipped with smoke detectors connected to the fire alarm system, (d) public corridors on each floor area are subdivided in accordance with Sentence (3), or (e) the building is fully sprinklered. (3) The public corridor subdivision referred to in Clause (2)(d) shall (a) separate the corridor into at least two compartments by a fire separation, (b) be located so that no more than one of the required exit stairs is located in any one compartment and the distance of travel from any suite entrance door to an exit or adjacent compartment does not exceed 25 m, and (c) include smoke-tight doors equipped with self-closing devices that act as closures in the fire separation. Subsection 9.6.3. Means of Egress Access to exits