fire code, O. Reg. 213/07
Section 9.5.3.3
Cite as fire code, O. Reg. 213/07, s. 9.5.3.3 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) Each exit stairway shall be separated from the remainder of the building by a fire separation having a fire-resistance rating not less than 45 min.
(2) If the building is 3 storeys or less in building height, a fire separation having a fire-resistance rating not less than 30 min is deemed to comply with Sentence (1).
(3) Closures in stairway fire separations referred to in Sentences (1) and (2) shall be equipped with self-closing devices.
Door swing
Read the fire code on e-Laws ↗
Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.