fire code, O. Reg. 213/07
Section 9.5.2.9
Cite as fire code, O. Reg. 213/07, s. 9.5.2.9 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) Storage rooms for the use of occupants, not contained within a dwelling unit or suite,
(a) shall be separated from the remainder of the building by a fire separation having a fire-resistance rating not less than 45 min, and
(b) shall be
(i) sprinklered, or
(ii) subdivided into areas not exceeding 150 m2 by fire separations having a fire-resistance rating not less than 45 min and equipped with fire detectors connected to the fire alarm system.
(2) Existing storage rooms are deemed to be in compliance with Clause (1)(b) where the building
(a) contains not more than four dwelling units, or
(b) provides sleeping accommodation for not more than 10 persons.
(3) Existing storage rooms are deemed to be in compliance with Sentence (1) where sleeping rooms are not located on the same floor as the storage rooms and
(a) the building contains not more than four dwelling units, or
(b) provides sleeping accommodation for not more than 10 persons.
Fuel-fired appliance service rooms