fire code, O. Reg. 213/07
Section 9.5.2.10
Cite as fire code, O. Reg. 213/07, s. 9.5.2.10 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) Fuel-fired appliances shall be enclosed in a service room separated from the remainder of the building by a fire separation having a fire-resistance rating not less than 45 min if the building height is greater than 2 storeys or the building area is greater than 400 m2.
(2) Sentence (1) does not apply to a fuel-fired appliance that serves only one dwelling unit or suite.
(3) Despite Sentence (1), the fire-resistance rating of the fire separation above the service room is not required where
(a) the required vertical fire separation to a service room is provided, and
(b) the service room area is sprinklered
(i) with a spacing not exceeding 9.5 m2 per sprinkler head, and
(ii) so that the sprinklers provide a minimum average density of 6.5 L/min/m2 over the room area.