fire code, O. Reg. 213/07

Section 9.4.2.8

Cite as fire code, O. Reg. 213/07, s. 9.4.2.8 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) Closures in fire separations shall comply with the requirements of Sentences 3.1.6.4.(2), 3.1.6.7.(1) and 3.1.6.8.(1) and Article 3.1.6.9. of the 1986 Building Code. (2) Openings in a fire separation that is required to have a 30 min fire-resistance rating shall be protected with closures that have a fire-protection rating not less than 20 min. (3) Where Sentences (1) and (2) require (a) a 1.5 h fire-protection rating, existing hollow metal doors, with or without wired glass panels not exceeding 645 cm2, equipped with self-closing devices and existing hollow metal frames are deemed to be in compliance, (b) a 45 min fire-protection rating, existing hollow metal or kalamein doors, with or without wired glass, equipped with self-closing devices and existing hollow metal frames are deemed to be in compliance, (c) a 45 min fire-protection rating, existing wired glass screens set in fixed steel frames are deemed to be in compliance, or (d) a 20 min fire-protection rating, existing 45 mm solid core wood doors equipped with self-closing devices and existing solid wood frames are deemed to be in compliance. (4) Existing doors to bedrooms not conforming to Sentences (1) to (3) may be approved. (5) Despite Sentence (1), and except as permitted in Article 9.4.2.9., door assemblies required to have a 20 min fire-protection rating shall be equipped with self-closing devices. (6) Despite Sentences (1) and (2), fire dampers or fire stop flaps are not required in ducts at penetrations of an existing fire separation. Latches on bedroom doors
Read the fire code on e-Laws ↗

Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.