fire code, O. Reg. 213/07

Section 9.4.2.7

Cite as fire code, O. Reg. 213/07, s. 9.4.2.7 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) Floor areas containing rooms or areas used by the residents shall be separated into at least two zones by fire separations having a fire-resistance rating not less than 45 min. (2) Each zone required in Sentence (1) shall (a) contain at least one acceptable exit, and (b) be able to accommodate, in addition to its own occupants, the occupants of the adjacent zone, based on the requirements of 0.5 m2 of clear floor space per person, 1.6 m2 per person in a wheelchair, and 2.4 m2 for each bedridden patient as the occupancy requires. (3) A fire separation is not required under Sentence (1) where (a) the travel distance between exits does not exceed 9 m and the number of occupants on the floor area is not more than 10 persons, or (b) the floor area is served by exterior exit doors leading directly to the outside. Protection of openings in fire separations
Read the fire code on e-Laws ↗

Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.