fire code, O. Reg. 213/07

Section 9.2.3.7

Cite as fire code, O. Reg. 213/07, s. 9.2.3.7 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) The aggregate required width of exits shall be determined by multiplying the occupant load of the area served by (a) 6.1 mm (1/4 in) per person for ramps with a gradient of not more than 1 in 8, doorways, corridors and passageways, or (b) 9.2 mm (3/8 in) per person for ramps with a gradient of more than 1 in 8 and stairs.
Read the fire code on e-Laws ↗

Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.