fire code, O. Reg. 213/07
Section 9.2.3.6
Cite as fire code, O. Reg. 213/07, s. 9.2.3.6 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) The minimum number of exits from a floor area shall be,
(a) for an occupant load of 61 up to and including 600 persons, not less than two exits,
(b) for an occupant load of 601 up to and including 1000 persons, not less than three exits, or
(c) for an occupant load of more than 1000 persons, not less than four exits.
Total width
Read the fire code on e-Laws ↗
Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.