fire code, O. Reg. 213/07
Section 8.1.2.8
Cite as fire code, O. Reg. 213/07, s. 8.1.2.8 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) Portable extinguishers shall be provided in buildings under demolition in accordance with Subsection 6.2.6. as if the buildings were graded for ordinary hazard under Subsection 6.2.5.
(2) In addition to the other requirements of this Code, if a building is under demolition, portable extinguishers shall be provided in unobstructed and easily accessible locations in any areas
(a) where hot work operations are carried out,
(b) where combustibles are stored,
(c) near or on any internal combustion engines,
(d) where flammable liquids and combustible liquids or gases are stored or handled,
(e) where temporary fuel-fired equipment is used,
(f) that are designated for smoking, and
(g) where bitumen heating equipment is used.
(3) The extinguishers required by Sentence (2) shall have a minimum rating of
(a) 3A:20B:C on moveable equipment, and
(b) 4A:40B:C in all other locations.
(4) Portable extinguishers required in Sentences (1), (2) and (3) shall be maintained in conformance with Section 6.2.
Smoking prohibited
Read the fire code on e-Laws ↗