fire code, O. Reg. 213/07

Section 7.3.1.4

Cite as fire code, O. Reg. 213/07, s. 7.3.1.4 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

Where vestibules, stairshafts or other areas are pressurized as a means of smoke control, all doors in the path of exit travel shall be tested to ensure that the doors can be operated as required in Article 2.7.2.1. when the entire smoke control system is being tested.