fire code, O. Reg. 213/07

Section 7.3.1.3

Cite as fire code, O. Reg. 213/07, s. 7.3.1.3 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) Subject to Sentences (2) to (5), where a smoke control system is designed to meet the requirements of the Building Code, the inspections and tests for equipment shall be carried out in accordance with procedures established by the designer of the system. (2) Where procedures described in Sentence (1) are not available, smoke control systems shall be assessed to ensure satisfactory operation and, where applicable, using techniques described in MMAH Supplementary Standard SB-4, “Measures for Fire Safety in High Buildings”. (3) Upon completion of the assessment described in Sentence (2), written procedures for periodic inspections and tests shall be established. (4) The procedures described in Sentence (3) shall bear the signature and seal of a Professional Engineer or Architect. (5) The inspections and tests established under Sentence (3) shall be implemented. (6) Despite Sentences (1) and (3), other inspection and test procedures may be approved. Doors in means of egress
Read the fire code on e-Laws ↗

Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.