fire code, O. Reg. 213/07

Section 6.3.2.6

Cite as fire code, O. Reg. 213/07, s. 6.3.2.6 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) This Article applies to interconnected smoke alarm systems in all residential occupancies and care occupancies, except in individual dwelling units and in buildings regulated by Section 9.8. (2) Interconnected smoke alarms shall be tested and maintained in operating condition in conformance with CAN/ULC-S552, “Standard for the Maintenance and Testing of Smoke Alarms”, and as required by this Article. (3) The power supply shall be checked weekly. (4) The operability of the interconnected system shall be confirmed monthly, by testing at least one smoke alarm using its test function, on a rotational basis. (5) Where installed, each manual pull station shall be tested to ensure activation of the interconnected smoke alarms on an annual basis. (6) Written records shall be kept of weekly checks of the power supply for at least six months after they are made, and be available upon request to the Chief Fire Official. (7) Revoked: O. Reg. 33/19, s. 23. Residential fire warning systems
Read the fire code on e-Laws ↗

Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.