fire code, O. Reg. 213/07

Section 6.3.2.5

Cite as fire code, O. Reg. 213/07, s. 6.3.2.5 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) Voice communication systems that are not integrated with a fire alarm system shall be tested monthly in compliance with Sentences (2) and (3). (2) Loudspeakers described in Sentence (1) shall be tested monthly as an all-call signal to ensure they function as intended. (3) Communication from at least one remote firefighter emergency telephone location to the control unit shall be tested monthly on a rotational basis so that communication from all remote firefighter emergency telephone locations are tested at least once per year. (4) Voice communication systems are not required to be tested in conformance with Sentences (1) and (2) where the systems are regularly used as part of a paging system. Interconnected smoke alarms
Read the fire code on e-Laws ↗

Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.