fire code, O. Reg. 213/07
Section 5.4.3.5
Cite as fire code, O. Reg. 213/07, s. 5.4.3.5 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) Where quantities exceed 3400 kg but do not exceed 9000 kg, cellulose nitrate plastics shall be stored in a vault that
(a) has a fire-resistance rating not less than 4 h,
(b) is designed to resist an internal pressure of 28 kPa,
(c) has explosion venting of 650 cm2 of venting area to the exterior for every cubic metre of vault volume, and
(d) is ventilated to the exterior to provide 200 cm2 of ventilating area for each cubic metre of vault volume.
Subsection 5.4.4. Cellulose Nitrate Motion Picture Film
Restricted use
Read the fire code on e-Laws ↗
Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.