fire code, O. Reg. 213/07
Section 5.4.3.4
Cite as fire code, O. Reg. 213/07, s. 5.4.3.4 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) Where quantities do not exceed 3400 kg, cellulose nitrate plastics shall be stored in a vault that
(a) has a fire-resistance rating not less than 1.5 h,
(b) is designed to resist an internal pressure of 3.5 kPa,
(c) is not greater than 40 m3 in volume,
(d) has explosion venting of 0.1 m2 of venting area to the exterior for every cubic metre of vault volume, and
(e) is ventilated to the exterior to provide 200 cm2 of ventilating area for each cubic metre of vault volume.
Storage in excess of 3400 kg
Read the fire code on e-Laws ↗
Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.