fire code, O. Reg. 213/07
Section 5.18.3.4
Cite as fire code, O. Reg. 213/07, s. 5.18.3.4 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) Ducts, stacks and associated insulation in systems for the removal of flammable vapours shall
(a) be constructed of noncombustible materials,
(b) not pass through firewalls, and
(c) discharge outdoors not less than
(i) 1.5 m from unprotected building openings, and
(ii) 6 m from air intake openings.
Subsection 5.18.4. Ventilation
Oven ventilation
Read the fire code on e-Laws ↗
Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.