fire code, O. Reg. 213/07

Section 5.18.3.3

Cite as fire code, O. Reg. 213/07, s. 5.18.3.3 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) Explosion vents shall be provided for ovens where fuel or vapour hazards are present. (2) Explosion vents shall be designed in accordance with NFPA 68, “Standard on Explosion Protection by Deflagration Venting”. (3) Existing explosion vents that provide a vent ratio of 0.2 m2 of vent area for each cubic metre of oven volume are deemed to satisfy the vent ratio for the purposes of NFPA 68 in Sentence (1). (4) Openings or access doors equipped with explosion release hardware shall be acceptable as explosion vents. Duct and stack restrictions