fire code, O. Reg. 213/07
Section 5.12.9.4
Cite as fire code, O. Reg. 213/07, s. 5.12.9.4 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) Spray booths may be used for drying operations where
(a) the spray booth conforms to the appropriate requirements for drying ovens in Section 5.18,
(b) the interior of the enclosure is kept reasonably free of overspray deposits,
(c) portable drying apparatus, if used, is of the infrared type, and such apparatus, wiring and connections are removed from the enclosure during spraying operations, and
(d) interlocks are installed to
(i) prevent the use of spraying apparatus while the drying operation is taking place,
(ii) provide for the purging of the enclosure of spray vapours for a minimum of 3 min before the drying apparatus can be energized,
(iii) ensure that the ventilating system maintains the concentration of flammable vapours at or below 25% of the lower explosive limit within the enclosure during the drying process, and
(iv) ensure that the drying apparatus will automatically shut off in the event of failure of the ventilating system.
Subsection 5.12.10. Electrostatic Spraying
Application
Read the fire code on e-Laws ↗
Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.