fire code, O. Reg. 213/07

Section 5.12.9.3

Cite as fire code, O. Reg. 213/07, s. 5.12.9.3 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) Equipment described in Article 5.12.9.2. may be installed in an area adjacent to the spraying area provided the adjacent area is equipped with a ventilating system arranged to (a) purge the drying space before the heating system can be started, (b) maintain the atmosphere at any source of ignition at or below 25% of the lower explosive limit of any combustible or flammable materials in use, and (c) automatically shut down the heating system in the event of failure of the ventilating system. Spray booths used for drying
Read the fire code on e-Laws ↗

Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.