fire code, O. Reg. 213/07
Section 5.12.10.3
Cite as fire code, O. Reg. 213/07, s. 5.12.10.3 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) Electrostatic spraying equipment shall be provided with automatic controls that will operate without a time delay to disconnect power to high voltage transformers and to signal the operator of the equipment if
(a) the air supply system, the ventilating fan or the conveyor system stops,
(b) a ground occurs at any point on the high voltage system, or
(c) any clearances are reduced below those required by Article 5.12.10.5.