fire code, O. Reg. 213/07
Section 5.12.10.2
Cite as fire code, O. Reg. 213/07, s. 5.12.10.2 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) Electrical components, including transformers, power packs and control equipment for electrostatic spray applications, shall be located in an area where the vapour concentration of flammable liquids or combustible liquids cannot exceed 25% of the lower explosive limit.
(2) Sentence (1) does not apply to high voltage grids and their connections.
Interlocks
Read the fire code on e-Laws ↗
Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.