fire code, O. Reg. 213/07

Section 4.5.6.9

Cite as fire code, O. Reg. 213/07, s. 4.5.6.9 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) Indoor piping for flammable liquids or combustible liquids shall either be supported overhead or be located in trenches conforming to Article 4.5.6.10. (2) Piping referred to in Sentence (1) shall not be installed under combustible flooring. (3) Piping in trenches referred to in Sentence (1) shall be covered with noncombustible material. Piping in trenches