fire code, O. Reg. 213/07

Section 4.5.6.8

Cite as fire code, O. Reg. 213/07, s. 4.5.6.8 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) Piping for flammable liquids or combustible liquids shall be located aboveground where the piping enters a building. (2) Piping referred to in Sentence (1) shall be provided with inside and outside shut-off valves. (3) Where piping referred to in Sentence (1) passes through a wall that would restrict the expansion or contraction of the piping, pipe sleeves shall be provided at the wall penetration to facilitate such movement. Indoor piping
Read the fire code on e-Laws ↗

Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.