fire code, O. Reg. 213/07
Section 4.5.6.5
Cite as fire code, O. Reg. 213/07, s. 4.5.6.5 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) Underground piping shall be located so it will not be damaged as a result of vibrations or settling of an adjacent building or structure.
(2) Underground piping shall be located not less than 300 mm away from the foundations of any building or structure, except where such piping enters the building as permitted in Article 4.5.6.8.
(3) Piping passing under railway tracks shall be installed in conformance with TC 2001, “Standards Respecting Pipeline Crossings Under Railways”.
(4) Piping adjacent to railway tracks shall be installed in conformance with the Flammable Liquids Bulk Storage Regulations, C.R.C., c1148, made under the Railway Safety Act (Canada).
Installation of underground piping
Read the fire code on e-Laws ↗
Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.