fire code, O. Reg. 213/07

Section 4.5.6.4

Cite as fire code, O. Reg. 213/07, s. 4.5.6.4 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) Aboveground outdoor piping shall not be located (a) on the exterior of walls except on those of noncombustible construction, or (b) above windows and doors. (2) Aboveground outdoor piping shall not be located above roofs except above roofs of impermeable and noncombustible construction, with provision for accidental spillage provided in conformance with Subsection 4.1.6. (3) Where aboveground piping crosses roadways or railway sidings, ample overhead clearance and warning signs indicating the clearance height shall be provided. (4) Piping passing though the secondary containment walls of an aboveground storage tank shall be designed to prevent excessive stress resulting from settlement or fire exposure. Arrangement of underground piping