fire code, O. Reg. 213/07
Section 4.3.9.1
Cite as fire code, O. Reg. 213/07, s. 4.3.9.1 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) A dispenser sump shall be provided under a dispenser, unless the dispenser is located on top of an aboveground storage tank.
(2) A spill containment sump shall be provided at every underground storage tank fill point.
(3) A transition sump shall be provided for all mechanical pipe connections located below grade.
(4) A turbine sump shall be provided for all turbine pump assemblies located below grade or above grade where they are not readily visible.
(5) In addition to the requirements of Article 4.3.9.2., the sumps referred to in Sentences (1) to (4) shall be installed in conformance with the sump manufacturer’s instructions.
Construction
Read the fire code on e-Laws ↗
Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.