fire code, O. Reg. 213/07

Section 4.3.8.9

Cite as fire code, O. Reg. 213/07, s. 4.3.8.9 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) Underground storage tanks shall be protected against hydrostatic forces which can cause the uplift of the tanks once they are empty. (2) Where anchors and ground straps are used to resist the uplift forces referred to in Sentence (1), they shall be (a) electrically isolated from the tank, and (b) installed in such a manner that they do not damage the tank's shell, protective coating, fittings or anodes. Subsection 4.3.9. Sumps Installation