fire code, O. Reg. 213/07
Section 4.3.8.3
Cite as fire code, O. Reg. 213/07, s. 4.3.8.3 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) Except as required in Sentences (2) to (4), underground storage tanks shall be installed with not less than 600 mm of ground cover over the tank.
(2) Except as required in Sentence (3), storage tanks subjected to vehicular traffic shall be installed not less than 1 m below finished ground level.
(3) Either a 150 mm reinforced concrete slab or a 200 mm unreinforced concrete slab over not less than 450 mm of sand is permitted in lieu of the protection described in Sentence (2) provided the slab extends at least 300 mm beyond the storage tank.
(4) Where subsurface conditions make it impracticable to install a storage tank totally below adjacent ground level, an underground storage tank shall be installed so that at least
(a) 75% of its mass is below adjacent ground level, provided there is not less than 600 mm of ground cover over the portion of the tank above adjacent ground level, or
(b) 50% of its mass is below adjacent ground level, provided there is not less than 1 m of ground cover over the portion of the tank above adjacent ground level.