fire code, O. Reg. 213/07

Section 4.3.8.2

Cite as fire code, O. Reg. 213/07, s. 4.3.8.2 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) Underground storage tanks shall be located so that loads from building foundations and supports are not transmitted to the tank and the foundations of buildings will not be undermined during excavation. (2) Underground storage tanks shall be separated by a horizontal distance of not less than (a) 600 mm from adjacent underground tanks or structures, (b) 1 m from a building foundation or a street line, and (c) 1.5 m from other property lines. Ground cover
Read the fire code on e-Laws ↗

Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.