fire code, O. Reg. 213/07

Section 4.3.13.9

Cite as fire code, O. Reg. 213/07, s. 4.3.13.9 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) Where storage tanks for flammable liquids or combustible liquids are located outside of storage rooms conforming to Subsection 4.3.14. (a) provision shall be made to contain a spill equal to at least 100% of the volume of the largest storage tank, or to drain away spilled flammable liquids or combustible liquids, in conformance with Subsection 4.1.6., (b) the area in which the storage tank is located shall be ventilated in conformance with Subsection 4.1.7., where designated a Class 1, Zone 0, 1 or 2 hazardous location under the Electrical Safety Code made under the Electricity Act, 1998, and (c) all electrical equipment and wiring in the vicinity of the storage tank and the exterior vent shall be installed in conformance with Subsection 4.1.4. Vents
Read the fire code on e-Laws ↗

Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.