fire code, O. Reg. 213/07
Section 4.3.13.8
Cite as fire code, O. Reg. 213/07, s. 4.3.13.8 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
When two or more classes of liquids are stored in a single storage room referred to in Sentence 4.3.13.4.(1), the total quantity permitted for each class of liquid shall be calculated as follows:
qI / QI + (qII + IIIA) / (QII + IIIA) ≤ 1
where
qI = actual quantity of Class I liquids present, in litres,
qII + IIIA = actual quantity of Class II and IIIA liquids present, in litres
QI = maximum quantity of Class I liquids permitted in Table 4.3.13.4.A., in litres, and
QII + IIIA = maximum quantity of Class II and IIIA liquids permitted in Table 4.3.13.4.A., in litres.
Storage tanks outside storage rooms
Read the fire code on e-Laws ↗
Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.