fire code, O. Reg. 213/07

Section 4.3.13.5

Cite as fire code, O. Reg. 213/07, s. 4.3.13.5 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) Storage tanks with an individual capacity exceeding 2500 L but not exceeding 20000 L that are used in conformance with Table 4.3.13.4.B. shall be (a) of double-walled construction in conformance with CAN/ULC-S601, “Shop Fabricated Steel Aboveground Tanks for Flammable and Combustible Liquids”, and (b) monitored for leakage in conformance with Sentence 4.4.2.1.(7). (2) Storage tanks with an individual capacity exceeding 20000 L that are used in conformance with Table 4.3.13.4.B. shall (a) conform to ULC-S655, “Aboveground Protected Tank Assemblies for Flammable and Combustible Liquids”, and (b) be monitored for leakage in conformance with Sentence 4.4.2.1.(7). Piping systems