fire code, O. Reg. 213/07
Section 4.3.13.4
Cite as fire code, O. Reg. 213/07, s. 4.3.13.4 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) Except as provided in Subsection 4.2.8. and in Sentence (2), storage tanks for flammable liquids or combustible liquids shall be
(a) located in dedicated storage rooms conforming to Subsection 4.3.14., and
(b) located in conformance with Tables 4.3.13.4.A. and 4.3.13.4.B.
(2) When quantities greater than those permitted for incidental use in Subsection 4.2.8. are required for special process operations, storage tanks for flammable liquids or combustible liquids are permitted to be located outside of a storage room referred to in Sentence (1), provided that
(a) total quantities per fire compartment are not more than one-half the quantities permitted in Table 4.3.13.4.A.,
(b) they are located on the first storey, and
(c) the installation conforms to Articles 4.3.13.9. to 4.3.13.12. and 4.3.14.5.
(3) Table 4.3.13.4.A. does not apply to the storage of distilled beverage alcohol.
Table 4.3.13.4.A.
Read the fire code on e-Laws ↗
Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.