fire code, O. Reg. 213/07
Section 4.3.1.10
Cite as fire code, O. Reg. 213/07, s. 4.3.1.10 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) A storage tank that has been taken out of service shall not be reused for the storage of flammable liquids or combustible liquids unless it has been
(a) refurbished so as to conform to one of the standards listed in Sentence 4.3.1.2.(1),
(b) refurbished so as to conform to CAN/ULC-S676, “Standard for Refurbishing of Storage Tanks for Flammable and Combustible Liquids”, or
(c) refurbished in conformance with Sentence (2) or (3).
(2) A storage tank is permitted to be refurbished for aboveground use in conformance with
(a) API STD 653, “Tank Inspection, Repair, Alteration, and Reconstruction”, and
(b) STI/SPFA SP031, “Standard for Repair of Shop Fabricated Aboveground Tanks for Storage of Flammable and Combustible Liquids”.
(3) A storage tank is permitted to be refurbished for underground use in conformance with CAN/ULC-S669, “Standard for Internal Retrofit Systems for Underground Tanks for Flammable and Combustible Liquids”.
(4) A riveted storage tank shall not be relocated.
(5) A refurbished storage tank that is installed and currently in use, that met the requirements of this Code on December 31, 2025, as it read at the time, that was refurbished on or before that day and that continues to meet those requirements is deemed to comply with Sentence (1).