fire code, O. Reg. 213/07

Section 4.2.9.2

Cite as fire code, O. Reg. 213/07, s. 4.2.9.2 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) Storage rooms referred to in Article 4.2.9.1. shall be liquid-tight where the walls join the floor and shall be equipped with a liquid-tight ramped sill at any door opening in an interior wall. (2) Storage rooms referred to in Sentence (1) shall be designed to accommodate possible spills of flammable liquids and combustible liquids in conformance with Subsection 4.1.6. Aisles
Read the fire code on e-Laws ↗

Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.