fire code, O. Reg. 213/07
Section 4.2.9.1
Cite as fire code, O. Reg. 213/07, s. 4.2.9.1 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) Except as provided in Sentences (2) and (3), where flammable liquids and combustible liquids are stored in a room required in this Part, the storage densities averaged over the total room area and the total quantities of such liquids shall conform to Table 4.2.9.1.
(2) The maximum quantities and densities of flammable liquids and combustible liquids shown in Table 4.2.9.1. are permitted to be doubled provided the storage room is protected by an automatic fire suppression system conforming to Article 4.2.7.6.
(3) The maximum quantities of Class I liquids in an unprotected storage room with a fire separation having a fire-resistance rating of not less than 2 h shall
(a) not exceed those specified for unprotected storage in Table 4.2.7.5.A., and
(b) comply with Sentences 4.2.7.5.(4) and (5).
Table 4.2.9.1.
Read the fire code on e-Laws ↗
Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.