fire code, O. Reg. 213/07

Section 4.1.7.4

Cite as fire code, O. Reg. 213/07, s. 4.1.7.4 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) Except as provided in Article 4.1.7.6., the exhaust air outlet from a mechanical ventilation system required in Article 4.1.7.2. shall be (a) located outdoors, not less than 3 m from any building opening, and (b) arranged so that the exhaust air does not discharge toward any unprotected opening within 7.5 m of the discharge point. Make-up air