fire code, O. Reg. 213/07
Section 4.1.7.3
Cite as fire code, O. Reg. 213/07, s. 4.1.7.3 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) Ventilation air inlets and outlets within a room or enclosed space referred to in Article 4.1.7.1. shall be arranged so as to provide air movement in all portions of the room to prevent the accumulation of flammable vapours in conformance with Sentence 4.1.7.2.(3).
(2) Inlets and outlets conforming to Sentence (3) or (4) shall be deemed to have met the requirements of Sentence (1).
(3) Where the flammable vapour being removed is heavier than air or as dense as air
(a) at least one air inlet shall be located at a point near a wall and no higher than 300 mm from the floor, and
(b) at least one air outlet shall be located near the opposite wall, no higher than 300 mm from the floor.
(4) Where the flammable vapour being removed is lighter than air
(a) at least one air inlet shall be located at a point near a wall and no lower than 300mm from the ceiling, and
(b) at least one air outlet shall be located near the opposite wall, no lower than 300 mm from the ceiling.
Location of mechanical ventilation exhaust air outlets