fire code, O. Reg. 213/07
Section 4.1.4.1
Cite as fire code, O. Reg. 213/07, s. 4.1.4.1 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) Where flammable liquids or combustible liquids are present, electrical equipment shall conform to Electrical Safety Code made under the Electricity Act, 1998 for hazardous locations.
(2) Where refrigerators are used to store Class I liquids, they shall be designed so that
(a) electrical equipment located within the storage compartment, within the outer shell, on the door and on the door frame of the refrigerator is in conformance with Electrical Safety Code made under the Electricity Act, 1998 for Class I, Zone 0 or 1 hazardous locations based on the frequency of occurrence and duration of an explosive gaseous atmosphere, and
(b) electrical equipment mounted on the outside surface of the refrigerator is
(i) in conformance with Electrical Safety Code made under the Electricity Act, 1998 for Class I, Zone 2 hazardous locations, or
(ii) located above the top of the storage compartment.
Subsection 4.1.5. Fire Prevention and Protection
Additional fire protection equipment
Read the fire code on e-Laws ↗
Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.