fire code, O. Reg. 213/07

Section 4.1.3.1

Cite as fire code, O. Reg. 213/07, s. 4.1.3.1 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) Except as provided in Sentences (3) and (4), the flash point of liquids having a kinematic viscosity less than 6 cSt at 37.8°C and a flash point below 93.3°C shall be determined in conformance with ASTM D56, “Standard Test Method for Flash Point by Tag Closed Cup Tester”. (2) Except as provided in Sentences (3) and (4), the flash point of liquids having a kinematic viscosity of 6 cSt or more at 37.8°C or a flash point of 93.3°C or higher shall be determined in conformance with ASTM D93, “Standard Test Method for Flash Point by Pensky-Martens Closed Cup Tester”. (3) ASTM D3828, “Standard for Flash Point by Small Scale Closed Cup Tester”, is permitted to be used for testing aviation turbine fuels within the scope of this procedure. (4) ASTM D3278, “Standard Test Methods for Flash Point of Liquids by Small Scale Closed-Cup Apparatus”, is permitted to be used for paints, enamels, lacquers, varnishes and related products and their components having flash points between 0°C and 110°C and having a kinematic viscosity less than 150 St at 25°C. Subsection 4.1.4. Electrical Installations Hazardous locations