fire code, O. Reg. 213/07
Section 3.4.2.2
Cite as fire code, O. Reg. 213/07, s. 3.4.2.2 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) Battery charging installations for battery-powered industrial trucks shall be located
(a) at least 1.5 m from combustible materials,
(b) when serving more than two trucks, in well ventilated areas,
(c) in areas where flammable gases or vapours, combustible dusts or combustible fibres are not present in hazardous quantities, and
(d) in areas where precautions are taken to prevent ignition sources, such as open flames, sparks or electric arcs.
(2) Battery charging installations for battery-powered industrial trucks shall be equipped with at least one portable extinguisher having a minimum rating of 2A:30B:C.
(3) Facilities shall be provided at battery charging installations for flushing and neutralizing spilled electrolyte and for protecting charging apparatus from mechanical damage.
Training
Read the fire code on e-Laws ↗
Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.