fire code, O. Reg. 213/07

Section 3.4.2.1

Cite as fire code, O. Reg. 213/07, s. 3.4.2.1 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) Fuel-fired industrial trucks shall be stored in (a) detached buildings, (b) areas separated from the remainder of the storage area by a fire separation having a fire-resistance rating of not less than 1 h, or (c) areas where the vehicles do not create a fire hazard to the storage area. (2) Except as provided in Sentence (3), industrial trucks shall be refuelled only at designated locations outside buildings. (3) Industrial trucks that are fuelled by replaceable propane cylinders are permitted to have their cylinders replaced indoors provided (a) cylinder replacement is done at a safe location that is at least 7.5 m from ignition sources, open pits and underground entrances, (b) the cylinder valves are closed, and (c) when an automatic quick-­closing coupling that closes in both directions when uncoupled and listed to ANSI/UL 558, “Industrial Trucks, Internal Combustion Engine‑Powered”, is not provided, the engine is operated until the fuel in the system is consumed. (4) Each fuel-fired industrial truck shall be equipped with at least one portable extinguisher having a minimum rating of 2A:30B:C. (5) Propane cylinders shall be stored in conformance with Section 5.6. Battery-powered industrial trucks
Read the fire code on e-Laws ↗

Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.