fire code, O. Reg. 213/07
Section 3.2.2.3
Cite as fire code, O. Reg. 213/07, s. 3.2.2.3 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) The clearance between sprinkler head deflectors and the top of any storage shall not be less than 457 mm.
(2) Where the top of any storage is above the lower chords of floor or roof structural framing members, a horizontal clear space of at least 300 mm shall be maintained between the storage and the structural members.