fire code, O. Reg. 213/07

Section 3.2.2.2

Cite as fire code, O. Reg. 213/07, s. 3.2.2.2 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) An individual storage area shall not exceed 500 m2 in buildings that are not sprinklered. (2) An individual storage area shall not exceed 1000 m2 in sprinklered buildings. (3) Heights of storage in buildings that are not sprinklered shall not exceed 4.5 m. (4) The maximum height of storage of any individual storage area shall be determined according to (a) the stability of the stored products as it relates to the base area and shape, and (b) the height limitations otherwise set in this Subsection. (5) Buildings containing individual storage areas that exceed 6.4 m in height shall be protected with (a) a sprinkler system designed and installed in accordance with NFPA 13, “Standard for the Installation of Sprinkler Systems”, or (b) a sprinkler system installed before January 1, 2015 that has been approved. Pile clearance
Read the fire code on e-Laws ↗

Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.