Electrical distribution safety, O. Reg. 22/04
Section 11
Disconnection of unused lines
Cite as Electrical distribution safety, O. Reg. 22/04, s. 11 · current to November 11, 2026 · consolidated from October 1, 2017 · read from e-Laws on November 16, 2026
The text
(1) A distributor shall disconnect and ground distribution lines of 750 volts or more that have not been in use for a prolonged period of time. O. Reg. 22/04, s. 11 (1).
(2) Prior to disconnecting and grounding the lines, the distributor shall de-energize them. O. Reg. 22/04, s. 11 (2).
(3) A distributor is not required to comply with subsection (1) where the lines, although unused, act as back-up or emergency lines. O. Reg. 22/04, s. 11 (3).
(4) A distributor is not required to comply with subsection (1) where the distributor provides the Authority with a report from, and a certificate signed by, a professional engineer indicating that,
(a) disconnecting and grounding the lines is not practical in the circumstances; and
(b) no undue danger to the safety of any person will be caused if the lines are not disconnected and grounded. O. Reg. 22/04, s. 11 (4).
Read the Electrical distribution safety on e-Laws ↗
Made under Electricity Act, 1998, S.O. 1998, c. 15, Sched. A.