SCHEDULE 7 OPERATIONAL CHECKS
Municipal: Large Residential Small Residential
Application
7-1. This Schedule applies to the following drinking water systems.
1. Large municipal residential systems.
2. Small municipal residential systems.
Chlorine residual
7-2. (1) The owner of a drinking water system that provides chlorination for primary disinfection shall ensure that sampling and testing for free chlorine residual is carried out by continuous monitoring equipment in the treatment process at or near a location where the intended contact time has just been completed in accordance with the Ministry’s Procedure for Disinfection of Drinking Water in Ontario.
(2) The owner of a drinking water system that provides chloramination for primary disinfection shall ensure that sampling and testing for combined chlorine residual is carried out by continuous monitoring equipment in the treatment process at or near a location where the intended contact time has just been completed in accordance with the Ministry’s Procedure for Disinfection of Drinking Water in Ontario.
(3) The owner of a large municipal residential system that provides secondary disinfection and the operating authority for the system shall ensure that at least seven distribution samples are taken each week in accordance with subsection (4) and are tested immediately for,
(a) free chlorine residual, if the system provides chlorination and does not provide chloramination; or
(b) combined chlorine residual, if the system provides chloramination.
(4) The following rules apply to the distribution samples referred to in subsection (3) unless at least one sample is taken on each day of the week:
1. At least four of the samples must be taken on one day of the week, at least 48 hours after the last sample was taken in the previous week.
2. At least three of the samples must be taken on a second day of the week, at least 48 hours after the last sample was taken on the day referred to in paragraph 1.
3. When more than one sample is taken on the same day of the week under paragraph 1 or 2, each sample must be taken from a different location.
(5) The owner of a small municipal residential system that provides secondary disinfection and the operating authority for the system shall ensure that at least two distribution samples are taken each week in accordance with subsection (6) and are tested immediately for,
(a) free chlorine residual, if the system provides chlorination and does not provide chloramination; or
(b) combined chlorine residual, if the system provides chloramination.
(6) At least one of the distribution samples referred to in subsection (5) must be taken at least 48 hours after, and during the same week as, one of the other distribution samples referred to in subsection (5).
Turbidity
7-3. (1) The owner of a drinking water system and the operating authority for the system shall ensure that a water sample is taken at least once every month, from a location that is before raw water enters the treatment system, and is tested for turbidity.
(1.1) If the drinking water system obtains water from a raw water supply that is ground water, the owner of the system and the operating authority for the system shall ensure that a sample is taken under subsection (1) from each well that is supplying water to the system.
(2) If a drinking water system obtains water from a raw water supply that is surface water and the system provides filtration,
(a) subsection (1) does not apply; and
(b) the owner of the system shall ensure that sampling and testing for turbidity is carried out by continuous monitoring equipment on each filter effluent line.
Fluoride
7-4. If a drinking water system provides fluoridation, the owner of the system and the operating authority for the system shall ensure that a water sample is taken at the end of the fluoridation process at least once every day and is tested for fluoride.
Testing by certified operators, emergency substitute operators or water quality analysts
7-5. (1) The owner of a drinking water system and the operating authority for the system shall ensure that every test required by this Schedule is conducted by a certified operator, emergency substitute operator or water quality analyst.
(1.1) Despite subsection (1), a test required by section 7-2 or 7-3 at a small municipal residential system may be conducted by a person who is not a certified operator, emergency substitute operator or water quality analyst if the person,
(a) has been trained by a certified operator to conduct the test;
(b) works under the supervision of a certified operator or an emergency substitute operator described in paragraph 1 or 2 of subsection 33 (1) of Ontario Regulation 128/04 (Certification of Drinking Water System Operators and Water Quality Analysts), made under the Act; and
(c) immediately advises a certified operator or an emergency substitute operator described in paragraph 1 or 2 of subsection 33 (1) of Ontario Regulation 128/04 (Certification of Drinking Water System Operators and Water Quality Analysts), made under the Act, of all test results.
(2) Subsection (1) does not apply to tests conducted by continuous monitoring equipment.