drinking water systems, O. Reg. 170/03
Schedule 6
Cite as drinking water systems, O. Reg. 170/03, Schedule 6 · current to November 11, 2026 · consolidated from April 11, 2022 · read from e-Laws on November 16, 2026
The text
SCHEDULE 6 OPERATIONAL CHECKS, SAMPLING AND TESTING — GENERAL
Application
6-1. This Schedule applies to the following drinking water systems:
1. Large municipal residential systems.
2. Small municipal residential systems.
3. Large municipal non-residential systems.
4. Small municipal non-residential systems.
5. Non-municipal year-round residential systems.
6. Non-municipal seasonal residential systems.
7. Large non-municipal non-residential systems.
8. Small non-municipal non-residential systems.
Frequency of sampling and equipment checks
6-1.1 (1) If this Regulation or an approval, municipal drinking water licence or order, including an OWRA approval or OWRA order, requires at least one water sample to be taken every week and tested for a parameter, the owner of the drinking water system and the operating authority for the system shall ensure that at least one sample that is taken during a week for the purpose of being tested for that parameter is taken at least five days, and not more than 10 days, after a sample was taken for that purpose in the previous week.
(2) If this Regulation or an approval, municipal drinking water licence or order, including an OWRA approval or OWRA order, requires at least one water sample to be taken every two weeks and tested for a parameter, the owner of the drinking water system and the operating authority for the system shall ensure that at least one sample that is taken during a two-week period for the purpose of being tested for that parameter is taken at least 10 days, and not more than 20 days, after a sample was taken for that purpose in the previous two-week period.
(3) If this Regulation or an approval, municipal drinking water licence or order, including an OWRA approval or OWRA order, requires at least one water sample to be taken every month and tested for a parameter, the owner of the drinking water system and the operating authority for the system shall ensure that at least one sample that is taken during a month for the purpose of being tested for that parameter is taken at least 20 days, and not more than 40 days, after a sample was taken for that purpose in the previous month.
(4) If this Regulation or an approval, municipal drinking water licence or order, including an OWRA approval or OWRA order, requires at least one water sample to be taken every three months or in each calendar quarter and tested for a parameter, the owner of the drinking water system and the operating authority for the system shall ensure that at least one sample that is taken during a three-month period or calendar quarter for the purpose of being tested for that parameter is taken at least 60 days, and not more than 120 days, after a sample was taken for that purpose in the previous three-month period or calendar quarter.
(5) If this Regulation or an approval, municipal drinking water licence or order, including an OWRA approval or OWRA order, requires at least one water sample to be taken every 12 months and tested for a parameter, the owner of the drinking water system and the operating authority for the system shall ensure that at least one sample that is taken during a 12-month period for the purpose of being tested for that parameter is taken not more than 30 days before or after the first anniversary of the day a sample was taken for that purpose in the previous 12-month period.
(6) If this Regulation or an approval, municipal drinking water licence or order, including an OWRA approval or OWRA order, requires at least one water sample to be taken every 36 months and tested for a parameter, the owner of the drinking water system and the operating authority for the system shall ensure that at least one sample that is taken during a 36-month period for the purpose of being tested for that parameter is taken not more than 60 days before or after the third anniversary of the day a sample was taken for that purpose in the previous 36-month period.
(7) If this Regulation or an approval, municipal drinking water licence or order, including an OWRA approval or OWRA order, requires at least one water sample to be taken every 60 months and tested for a parameter, the owner of the drinking water system and the operating authority for the system shall ensure that at least one sample that is taken during a 60-month period for the purpose of being tested for that parameter is taken not more than 90 days before or after the fifth anniversary of the day a sample was taken for that purpose in the previous 60-month period.
(8) This section applies, with necessary modifications, if this Regulation or an approval, drinking water works permit, municipal drinking water licence or order, including an OWRA approval or OWRA order, requires equipment to be checked at intervals to which any of subsections (1) to (7) apply.
Location of samples
6-2. Unless otherwise specified, a person who is required to ensure that samples are taken under this Regulation, or under an approval, municipal drinking water licence or order, including an OWRA order, shall ensure that they are taken from the point at which water enters the drinking water systems’ distribution system or plumbing that is connected to the drinking water system.
Microbiological samples and chlorine residual
6-3. (1) If this Regulation or an approval, municipal drinking water licence or order, including an OWRA order, requires a water sample to be taken and tested for a microbiological parameter, the owner of the drinking water system and the operating authority for the system shall ensure that another sample is taken at the same time from the same location and is tested immediately for,
(a) free chlorine residual, if the system provides chlorination and does not provide chloramination; or
(b) combined chlorine residual, if the system provides chloramination.
(2) Subsection (1) does not apply to water samples taken from the drinking water system’s raw water or raw water supply.
(3) Subsection (1) does not apply to sampling and testing for a microbiological parameter that is conducted by microbiological in-line testing equipment.
Form of sampling
6-4. (1) A person who is required to ensure that samples are taken under this Regulation, or under an approval, municipal drinking water licence or order, including an OWRA order, shall ensure that they are taken in the form of grab samples, unless continuous monitoring equipment or microbiological in-line testing equipment is authorized or required.
(2) Continuous monitoring equipment may be used for sampling and testing that is required under this Regulation, or under an approval, municipal drinking water licence or order, for,
(a) turbidity;
(b) fluoride;
(c) free chlorine residual; and
(d) free chlorine residual and total chlorine residual measured for the purpose of determining combined chlorine residual.
(3) Microbiological in-line testing equipment may be used for sampling and testing for a microbiological parameter that is required under this Regulation, or under an approval, municipal drinking water licence or order, if the Director is of the opinion that the testing method used by the equipment and the person operating the equipment is equivalent to a testing method for the parameter that is accredited by an accreditation body for drinking water testing that is designated or established under the Act.
Continuous monitoring
6-5. (1) If a drinking water system uses continuous monitoring equipment for sampling and testing that is required under this Regulation, or under an approval, drinking water works permit, municipal drinking water licence or order, for a parameter set out in the Table to this section, the owner of the system and the operating authority for the system shall ensure that the following standards are met:
1. The continuous monitoring equipment must, except when no water is being directed to users of water sampled by the equipment,
i. test for the parameter with at least the minimum frequency specified in the Table for the parameter, and
ii. record the date, time, sampling location and result of every test for the parameter with at least the minimum frequency referred to in subparagraph i.
2. If the continuous monitoring equipment tests for a parameter more often than is required by subparagraph 1 i, the equipment may, instead of complying with subparagraph 1 ii,
i. record the minimum, maximum and mean results of tests for the parameter for every period that is equal to the length of time referred to in subparagraph 1 i, along with the sampling location, the date of the tests conducted during the period and the time at the end of the period, and
ii. record the result of every test that causes an alarm to signal under paragraph 1 of subsection (1.1), along with the sampling location and the date and time of the test.
3. Test results recorded under paragraph 1 or 2 must be examined, within 72 hours after the tests are conducted,
i. by a certified operator or emergency substitute operator, in the case of,
A. a large municipal residential system,
B. a small municipal residential system,
C. a large municipal non-residential system,
D. a non-municipal year-round residential system, or
E. a large non-municipal non-residential system, or
ii. by a trained person, in the case of,
A. a non-municipal seasonal residential system,
B. a small municipal non-residential system, or
C. a small non-municipal non-residential system.
4. If test results are not examined under paragraph 3 at the location where the tests are conducted, the continuous monitoring equipment must transmit the results to the location where they are examined.
5. The continuous monitoring equipment must be designed and operated in accordance with the standards described in subsection (1.1), or,
i. the continuous monitoring equipment must have a feature that ensures that no water is directed to users of water sampled by the equipment in the event that the equipment malfunctions or loses power or a test result for a parameter is above the maximum alarm standard or below the minimum alarm standard specified in the Table to this section for the parameter, and
ii. if the continuous monitoring equipment malfunctions or loses power or a test result for a parameter is above the maximum alarm standard or below the minimum alarm standard specified in the Table to this section for the parameter, a person who is qualified to examine test results under paragraph 3 takes appropriate action at the location where tests are conducted before water is again directed to users of water sampled by the equipment.
6., 7. Revoked: O. Reg. 247/06, s. 17 (5).
8. The continuous monitoring equipment must be checked and calibrated in accordance with the manufacturer’s instructions.
9. If the manufacturer’s instructions do not indicate how often to check and calibrate the continuous monitoring equipment, the equipment must be checked and calibrated at least once a month while the drinking water system is in operation, in the case of,
i. a small municipal non-residential system,
ii. a non-municipal seasonal residential system, or
iii. a small non-municipal non-residential system.
10. If the manufacturer’s instructions do not indicate how often to check and calibrate the continuous monitoring equipment and paragraph 9 does not apply, the equipment must be checked and calibrated as often as necessary to ensure that test results are within the following margins of error:
i. In the case of free chlorine residual, 0.05 milligrams per litre, if the concentrations usually measured by the equipment are less than or equal to 1.0 milligrams per litre, and proportionally higher if the concentrations usually measured are greater than 1.0 milligrams per litre,
ii. In the case of free chlorine residual and total chlorine residual measured for the purpose of determining combined chlorine residual, 0.05 milligrams per litre, if the concentrations usually measured by the equipment are less than or equal to 1.0 milligrams per litre, and proportionally higher if the concentrations usually measured are greater than 1.0 milligrams per litre,
iii. 0.1 Nephelometric Turbidity Units (NTU), in the case of turbidity.
(1.1) The standards referred to in paragraph 5 of subsection (1) are the following:
1. The continuous monitoring equipment must cause an alarm to signal immediately at the following locations if the equipment malfunctions or loses power or a test result for a parameter is above the maximum alarm standard or below the minimum alarm standard specified in the Table to this section for the parameter:
i. The location where the equipment conducts tests.
ii. A location where a person is present, if a person is not always present at the location where the equipment conducts tests.
iii. Every designated facility served by the drinking water system, unless the system is a large municipal residential system or a small municipal residential system.
2. A person qualified to examine test results under paragraph 3 of subsection (1) must take appropriate action if the person is at the location where tests are conducted and,
i. an alarm signals under paragraph 1,
ii. a record of a test result indicates that an alarm should have signalled under paragraph 1, or
iii. there is good reason to believe that the continuous monitoring equipment has malfunctioned or lost power.
3. A person qualified to examine test results under paragraph 3 of subsection (1) must promptly be dispatched to the location where tests are conducted to take appropriate action if no person qualified to examine test results under paragraph 3 of subsection (1) is at that location and,
i. an alarm signals under paragraph 1, unless a person qualified to examine test results under paragraph 3 of subsection (1) determines that,
A. the alarm signalled because a test result for a parameter was above the maximum alarm standard or below the minimum alarm standard specified in the Table to this section for the parameter, and
B. within two minutes, a further test result indicated that the parameter was no longer above the maximum alarm standard or below the minimum alarm standard, as the case may be,
ii. a record of a test result indicates that an alarm should have signalled under paragraph 1, or
iii. there is good reason to believe that the continuous monitoring equipment has malfunctioned or lost power.
4. A person who is dispatched under paragraph 3 must arrive at the location where tests are conducted as soon as possible.
(2) For the purposes of the Table to this section, the concentration of free chlorine residual or combined chlorine residual that is required to achieve primary disinfection for the drinking water system shall be determined in accordance with the Ministry’s Procedure for Disinfection of Drinking Water in Ontario.
TABLE
Item | Parameter | Minimum Testing and Recording Frequency | Maximum Alarm Standard | Minimum Alarm Standard
1. | Free chlorine residual required to achieve primary disinfection | 5 minutes | Not applicable | 0.1 milligrams per litre less than the concentration of free chlorine residual that is required to achieve primary disinfection
2. | Free chlorine residual and total chlorine residual measured for the purpose of determining combined chlorine residual required to achieve primary disinfection | 5 minutes | Not applicable | 0.1 milligrams per litre less than the concentration of combined chlorine residual that is required to achieve primary disinfection
3. | Free chlorine residual in a distribution sample | 1 hour | Not applicable | 0.05 milligrams per litre
4. | Free chlorine residual and total chlorine residual measured for the purpose of determining combined chlorine residual in a distribution sample | 1 hour | Not applicable | 0.25 milligrams per litre
5. | Turbidity | 15 minutes | 1.0 Nephelometric Turbidity Units (NTU) | Not applicable
Turbidity testing
6-6. If a water sample is required to be taken and tested for turbidity, the owner of the drinking water system and the operating authority for the system shall ensure that the testing is conducted using a turbidity meter that measures turbidity in Nephelometric Turbidity Units (NTU).
Chlorine residual testing
6-7. (1) If a water sample is required to be taken and tested for free chlorine residual or combined chlorine residual, the owner of the drinking water system and the operating authority for the system shall ensure that the testing is conducted using,
(a) an electronic direct readout colourimetric or amperometric chlorine analyzer; or
(b) another device, if, based on an inspection of the device and on a review of relevant records and documentation, a licensed engineering practitioner states in writing that it is equivalent to or better than an electronic direct readout colourimetric or amperometric chlorine analyzer, having regard to accuracy, reliability and ease of use.
(2) Subsection (1) does not apply to testing that is conducted by continuous monitoring equipment.
Sample handling
6-8. If this Regulation or an approval, municipal drinking water licence or order, including an OWRA order, requires a water sample to be tested for a parameter by a laboratory, the owner of the drinking water system and the operating authority for the system shall ensure that, subject to the other provisions of this Regulation, the sample is taken and handled in accordance with the directions of the laboratory to which the sample will be delivered for testing, including directions with respect to,
(a) collection procedures;
(b) the use of specified kinds of containers or of containers that are provided by the laboratory;
(c) the labelling of samples;
(d) the completion and submission of forms that are provided by the laboratory;
(e) methods of transporting samples, including temperature conditions that must be maintained during transportation; and
(f) time periods for delivery of samples.
Testing by laboratories
6-9. (1) Revoked: O. Reg. 249/03, s. 12 (5).
(2) Revoked: O. Reg. 249/03, s. 12 (6).
(3) Revoked: O. Reg. 249/03, s. 12 (8).
(4) If a test of a water sample for a parameter is required by this Regulation, or by an approval, municipal drinking water licence or order, including an OWRA order, the owner of the drinking water system and the operating authority for the system shall ensure that written notice of the identity of the laboratory that will conduct the test is given to the Director before the sample is tested, unless,
(a) the Director has previously been notified under this subsection that a water sample from the drinking water system was to be tested for that parameter by that laboratory; or
(b) before this Regulation came into force, the Director was previously notified in accordance with Ontario Regulation 459/00 (Drinking Water Protection — Larger Water Works) or Ontario Regulation 505/01 (Drinking Water Protection — Smaller Water Works Serving Designated Facilities) that a water sample from the drinking water system was to be tested for that parameter by that laboratory.
(5) Revoked: O. Reg. 249/03, s. 12 (10).
(6) If a test of a water sample for a parameter is required by an approval, municipal drinking water licence or order, including an OWRA order, and the parameter is identified in the approval or order as a health-related parameter, the owner of the drinking water system and the operating authority for the system shall ensure that the laboratory that conducts the testing is informed, when the sample is sent to the laboratory, of the maximum concentration set out for the parameter in the approval or order.
(7)-(9) Revoked: O. Reg. 249/03, s. 12 (11).
Records
6-10. (1) The owner of a drinking water system and the operating authority for the system shall ensure that, for every sample required by this Regulation or by an approval, municipal drinking water licence or order, including an OWRA order, a record is made of the following information:
1. The date and time the sample was taken, the location where the sample was taken and the name of the person who took the sample.
2. If the sample is taken under section 7 of this Regulation or Schedule 7, 8 or 9, the date and time the sample was tested, the name of the person who conducted the test, and the results of the test.
3. If the sample is taken from a drinking water system’s distribution system under section 15.1-4 or 15.1-5 of Schedule 15.1, the addresses of all premises served by the plumbing from which samples were taken on the same day in accordance with subsection 15.1-6 (3).
4. If the sample is taken under section 15.1-7 of Schedule 15.1 and tested for pH,
i. the date and time of the test,
ii. the name of the person who conducted it, and
iii. the results of the test.
(2) Subsection (1) does not apply to a sample tested by continuous monitoring equipment or microbiological in-line testing equipment.
OWRA orders
6-11. If an OWRA order requires samples to be taken and tested for a parameter and a provision of Schedules 7 to 15.2 also requires samples to be taken and tested for the parameter, the provision of Schedules 7 to 15.2 prevails.
OWRA approvals
6-12. (1) If an OWRA approval requires more stringent sampling or testing than a provision of this Schedule or Schedules 7 to 15.2, the OWRA approval prevails.
(2) If an OWRA approval requires less stringent sampling or testing than a provision of this Schedule or Schedules 7 to 15.2, the provision of this Schedule or Schedules 7 to 15.2 prevails.
Read the drinking water systems on e-Laws ↗
Made under Safe Drinking Water Act, 2002, S.O. 2002, c. 32.