drinking water systems, O. Reg. 170/03
Schedule 2
Cite as drinking water systems, O. Reg. 170/03, Schedule 2 · current to November 11, 2026 · consolidated from April 11, 2022 · read from e-Laws on November 16, 2026
The text
SCHEDULE 2 TREATMENT EQUIPMENT
Municipal: Large Non-Residential Small Non-Residential
Non-Municipal: Year-Round Residential Seasonal Residential Large Non-Residential Small Non-Residential
Application
2-1. This Schedule applies to the following drinking water systems:
1. Large municipal non-residential systems.
2. Small municipal non-residential systems.
3. Non-municipal year-round residential systems.
4. Non-municipal seasonal residential systems.
5. Large non-municipal non-residential systems.
6. Small non-municipal non-residential systems.
General obligations
2-2. (1) The owner of a drinking water system shall ensure the following:
1. Any well that serves as an entry point of raw water supply is constructed and maintained to prevent surface water and other foreign materials from entering the well.
2. Water treatment equipment is provided in accordance with sections 2-3 to 2-5.
(2) The owner of a drinking water system and the operating authority for the system shall ensure the following:
1. The water treatment equipment is in operation whenever water is being supplied.
2. The water treatment equipment is operated in accordance with the Ministry’s Procedure for Disinfection of Drinking Water in Ontario.
3. The water treatment equipment required by section 2-3 or 2-4 is operated in a manner that achieves the design capabilities it is required to have under that section.
4. The water treatment equipment required by section 2-5 is operated so that, at all times and at all locations within the distribution system,
i. the free chlorine residual is never less than 0.05 milligrams per litre, if the drinking water system provides chlorination and does not provide chloramination, or
ii. the combined chlorine residual is never less than 0.25 milligrams per litre, if the drinking water system provides chloramination.
5. The water treatment equipment is properly maintained.
6. Written operating instructions for the water treatment equipment are kept near the equipment.
7. Clearly marked adequate supplies of chemicals or other materials necessary for the operation of the water treatment equipment are kept nearby, separate from other chemicals and materials that are not used for the drinking water system.
8. Replacement parts are kept nearby for those parts of the water treatment equipment that may be expected to require periodic replacement.
9. Adjustments to the water treatment equipment are carried out only by,
i. certified operators or emergency substitute operators, in the case of,
A. a large municipal non-residential system,
B. a non-municipal year-round residential system, or
C. a large non-municipal non-residential system, or
ii. trained persons, in the case of,
A. a small municipal non-residential system,
B. a non-municipal seasonal residential system, or
C. a small non-municipal non-residential system.
(3) Subsection (2) does not apply to a large municipal non-residential system, small municipal non-residential system, large non-municipal non-residential system or small non-municipal non-residential system on days when the system is not supplying water to any designated facilities or public facilities that are open.
(4) Subsection (2) does not apply to a non-municipal seasonal residential system during a period of 60 or more consecutive days when the system,
(a) is not supplying water to any designated facilities or public facilities that are open;
(b) is not supplying water to any major residential development; and
(c) is not supplying water to any trailer park or campground that has more than five service connections.
Primary disinfection for ground water raw water supply
2-3. (1) The owner of a drinking water system that obtains water from a raw water supply that is ground water shall ensure provision of water treatment equipment that is designed to be capable of achieving, at all times, primary disinfection in accordance with the Ministry’s Procedure for Disinfection of Drinking Water in Ontario, including at least 99 per cent removal or inactivation of viruses by the time,
(a) water leaves the point of entry treatment units, in the case of a drinking water system to which, pursuant to section 3-1.1 or 3-2 of Schedule 3, section 2-5 does not apply; or
(b) water enters the distribution system, in any other case.
(2) Subsection (1) also applies in respect of a non-municipal year-round residential system that is deemed, under paragraph 4 or 5 of subsection 2 (2), to obtain water from a raw water supply that is ground water under the direct influence of surface water if,
(a) the system does not serve any designated facilities; and
(b) the owner of the system gives the Director,
(i) a written notice that complies with section 2-12, and
(ii) a written notice stating that the owner of the system and the operating authority for the system have complied with section 11-3 of Schedule 11 and sections 18-5 and 18-6 of Schedule 18 for a period of 12 consecutive months and that, during that period,
(A) no test results from water samples described in subsection 11-3 (1) of Schedule 11 from the system’s raw water indicated the presence of Escherichia coli (E. coli) or total coliforms, and
(B) no test results from water samples taken under section 18-5 or 18-6 of Schedule 18 indicated the presence of Escherichia coli (E. coli) or total coliforms.
(3) Subsection (1) also applies, until the end of the month following the first anniversary of the day the system commences operation, in respect of a non-municipal year-round residential system that is deemed under paragraph 4 or 5 of subsection 2 (2) to obtain water from a raw water supply that is ground water under the direct influence of surface water, if,
(a) the system commences operation after this section comes into force;
(b) the system does not serve any designated facilities; and
(c) before the system commences operation, the owner of the system gives the Director a written notice that complies with section 2-12.
(4) Subsections (2) and (3) cease to apply to a non-municipal year-round residential system 90 days after,
(a) a test result obtained under paragraph 2 of section 18-5 of Schedule 18 indicates the presence of Escherichia coli (E. coli) in a water sample; or
(b) a test result obtained under paragraph 1 of section 18-6 of Schedule 18 indicates the presence of total coliforms in a water sample, if the day on which the sample was taken is the second day during a period of 12 consecutive months on which a water sample was taken under paragraph 1 of section 18-6 of Schedule 18 that produced a test result indicating the presence of total coliforms.
(5) No notice may be given to the Director under clause (2) (b) if subsection (2) or (3) previously ceased to apply to the system under subsection (4).
Filtration and primary disinfection for surface water raw water supply
2-4. (1) The owner of a drinking water system that obtains water from a raw water supply that is surface water shall ensure provision of,
(a) water treatment equipment that,
(i) is designed to be capable of chemically assisted filtration, and
(ii) is designed to be capable of achieving, at all times, primary disinfection in accordance with the Ministry’s Procedure for Disinfection of Drinking Water in Ontario, including at least 99 per cent removal or inactivation of Cryptosporidium oocysts, at least 99.9 per cent removal or inactivation of Giardia cysts and at least 99.99 per cent removal or inactivation of viruses by the time,
(A) water leaves the point of entry treatment units, in the case of a drinking water system to which, pursuant to section 3-1.1 or 3-2 of Schedule 3, section 2-5 does not apply, or
(B) water enters the distribution system, in any other case; or
(b) other water treatment equipment that, in the opinion of a licensed engineering practitioner, is designed to be capable of producing water of equal or better quality than the equipment described in clause (a).
(2) Subsection (1) does not apply in respect of a non-municipal year-round residential system if subsection 2-3 (1) applies in respect of the system.
Secondary disinfection
2-5. (1) The owner of a drinking water system shall ensure provision of,
(a) water treatment equipment that is designed to be capable of secondary disinfection using chlorination or chloramination in accordance with the Ministry’s Procedure for Disinfection of Drinking Water in Ontario and that is designed to be capable of achieving, at all locations within the distribution system,
(i) a free chlorine residual of 0.2 milligrams per litre, if the drinking water system provides chlorination and does not provide chloramination, or
(ii) a combined chlorine residual of 1.0 milligrams per litre, if the drinking water system provides chloramination; or
(b) other water treatment equipment that, in the opinion of a licensed engineering practitioner, is designed to be capable of providing secondary disinfection that is equivalent to or better than the secondary disinfection provided by the equipment described in clause (a).
(2) This section does not apply if,
(a) the owner complies with section 2-3 or 2-4, whichever is applicable; and
(b) all parts of the drinking water system and of the plumbing connected to the drinking water system that are downstream of the equipment provided in accordance with section 2-3 or 2-4 are enclosed in a building or other protective structure.
Primary disinfection equipment that does not use chlorination or chloramination
2-6. (1) If primary disinfection equipment that does not use chlorination or chloramination is provided by a drinking water system, the owner of the system and the operating authority for the system shall ensure that the disinfection equipment is designed and operated in accordance with the standards described in subsection (2), or that,
(a) the disinfection equipment has a feature that ensures that no water is directed to users of water treated by the equipment in the event that the equipment malfunctions, loses power or ceases to provide the appropriate level of disinfection; and
(b) if the disinfection equipment malfunctions, loses power or ceases to provide the appropriate level of disinfection, a person described in paragraph 9 of subsection 2-2 (2) takes appropriate action at the location where the equipment is installed before water is again directed to users of water treated by the equipment.
(2) The standards referred to in subsection (1) are the following:
1. The disinfection equipment must have a feature that causes an alarm to signal immediately in the following locations if the disinfection equipment malfunctions, loses power or ceases to provide the appropriate level of disinfection:
i. The building or structure where the disinfection equipment is installed.
ii. A location where a person is present, if a person is not always present at the building or structure where the disinfection equipment is installed.
2. If an alarm signals under paragraph 1, a person described in paragraph 9 of subsection 2-2 (2) who is at the building or structure where the disinfection equipment is installed must take appropriate action or, if no such person is at that location, a person described in paragraph 9 of subsection 2-2 (2) must promptly be dispatched to that location to take appropriate action.
3. A person who is dispatched under paragraph 2 must arrive at the building or structure where the disinfection equipment is installed as soon as possible.
(3) If a drinking water system provides primary disinfection with ultraviolet light disinfection equipment and not with chlorination or chloramination, the owner of the system and the operating authority for the system shall ensure that any sensors that form part of the equipment’s monitoring system are checked and calibrated in accordance with the manufacturer’s instructions.
OWRA approvals and OWRA orders with less stringent requirements
2-7. This Schedule prevails over an OWRA approval or OWRA order granted or issued before August 1, 2000 that provides for less stringent requirements.
OWRA approvals and OWRA orders that give additional time for compliance
2-8. If an OWRA approval or OWRA order granted or issued on or after August 1, 2000 provides that a drinking water system is required, by a date specified in the approval or order that is later than the date this Regulation comes into force,
(a) to comply with section 5 of Ontario Regulation 459/00 (Drinking Water Protection — Larger Water Works) or section 4 of Ontario Regulation 505/01 (Drinking Water Protection — Smaller Water Works Serving Designated Facilities); or
(b) to ensure that water treatment equipment is provided for primary disinfection, secondary disinfection or filtration,
sections 2-2 to 2-6 do not apply until the date specified in the approval or order.
Delayed compliance
2-9. Subject to section 2-8, if a non-municipal year-round residential system does not serve a designated facility, the system commenced operation before June 1, 2003 and, immediately before that day, the system was not in compliance with sections 2-2 to 2-6, those sections do not apply until July 1, 2006.
2-10. Revoked: O. Reg. 247/06, s. 14 (7).
Exceptions
2-11. (1) This Schedule, except paragraph 1 of subsection 2-2 (1), does not apply to a non-municipal year-round residential system if,
(a) the system does not serve any designated facilities;
(b) the system obtains water from a raw water supply that is ground water; and
(c) the owner of the system gives the Director,
(i) a written notice that complies with section 2-12, and
(ii) a written notice stating that the owner of the system and the operating authority for the system have complied with section 11-3 of Schedule 11 and sections 18-5 and 18-6 of Schedule 18 for a period of 12 consecutive months and that, during that period,
(A) no test results from water samples described in subsection 11-3 (1) of Schedule 11 from the system’s raw water indicated the presence of Escherichia coli (E. coli) or total coliforms, and
(B) no test results from water samples taken under section 18-5 or 18-6 of Schedule 18 indicated the presence of Escherichia coli (E. coli) or total coliforms.
(2) This Schedule, except paragraph 1 of subsection 2-2 (1), does not apply to a non-municipal year-round residential system until the end of the month following the first anniversary of the day the system commences operation if,
(a) the system commences operation after this section comes into force;
(b) the system does not serve any designated facilities;
(c) the system obtains water from a raw water supply that is ground water; and
(d) before the system commences operation, the owner of the system gives the Director a written notice that complies with section 2-12.
(3) Subsections (1) and (2) cease to apply to a non-municipal year-round residential system 90 days after,
(a) a test result obtained under paragraph 2 of section 18-5 of Schedule 18 indicates the presence of Escherichia coli (E. coli) in a water sample; or
(b) a test result obtained under paragraph 1 of section 18-6 of Schedule 18 indicates the presence of total coliforms in a water sample, if the day on which the sample was taken is the second day during a period of 12 consecutive months on which a water sample was taken under paragraph 1 of section 18-6 of Schedule 18 that produced a test result indicating the presence of total coliforms.
(4) No notice may be given to the Director under clause (1) (c) if subsection (1) or (2) previously ceased to apply to the system under subsection (3).
Well technician’s notice
2-12. (1) For the purpose of this Schedule, a notice complies with this section with respect to a non-municipal year-round residential system if the notice is signed by a person described in subsection (2) and the notice states that, after the day this section came into force, the person inspected each well that is used as a raw water supply for the system and, for each of those wells, the person is of the opinion that,
(a) the well does not have a well pit;
(b) the well does not penetrate through the bottom of a bored or dug well;
(c) the well is accessible for cleaning, treatment, repair, testing, inspection and visual examination at all times;
(d) the site of the well is at an elevation higher than the immediately surrounding area;
(e) the site of the well is separated by at least the clearance distance required by Ontario Regulation 332/12 (Building Code), made under the Building Code Act, 1992, from a leaching bed system or other sewage system as defined in that regulation, including a sewage system that has not been constructed but for which a building permit has been issued;
(f) the site of the well is at least 15 metres from a source of pollution other than one mentioned in clause (e);
(g) the well is cased to,
(i) at least 15 centimetres above the floor, if a pump is installed directly over the well and a floor has been constructed around or adjacent to the casing, or
(ii) at least 30 centimetres above the ground surface, in any other case;
(h) the surface drainage is such that water will not collect or pond in the vicinity of the well, including the area above the annular space;
(i) the top of the well’s casing is sealed with a commercially manufactured vermin-proof well cap, if a pump is not located directly over the well;
(j) the top of the well’s casing is shielded in a manner sufficient to prevent entry of any material that may impair the quality of the water in the well, if a pump is installed directly over the well;
(k) the well’s air vent extends above the ground surface a distance sufficient to prevent the entry of flood water from any anticipated flooding in the area;
(l) the open end of the well’s air vent is shielded and screened in a manner sufficient to prevent the entry of any materials into the well;
(m) the well’s casing does not impair the quality of water with which it comes in contact;
(n) the portion of the well’s casing that is visible without a down-hole camera,
(i) is clean and free of contamination, and
(ii) is watertight;
(o) the portion of the well’s casing that is visible without a down-hole camera has no joints, except for joints that,
(i) achieve a permanent, watertight bond, such as welded steel joints, and
(ii) are made so that the jointed casing does not impair the quality of water with which it comes in contact;
(p) any seams in the portion of the well’s casing that is visible without a down-hole camera achieve a permanent watertight bond; and
(q) a pitless adapter is used and the connection is watertight, if a connection to the casing of the well is made below the ground surface.
(2) The person referred to in subsection (1) is,
(a) a person who holds a well technician licence described as a Well Drilling licence in paragraph 1 of subsection 5 (1) of Regulation 903 of the Revised Regulations of Ontario, 1990 (Wells) made under the Ontario Water Resources Act;
(b) a licensed engineering practitioner who has experience in ground water supply;
(c) a professional hydrogeologist who has experience in ground water supply; or
(d) a person registered as a certified engineering technologist under the Ontario Association of Certified Engineering Technicians and Technologists Act, 1998 who has experience in ground water supply.
(3) Words and expressions used in this section have the same meanings as in section 35 of the Ontario Water Resources Act and section 1 of Regulation 903 of the Revised Regulations of Ontario, 1990 (Wells) made under that Act.