drinking water systems, O. Reg. 170/03
Schedule 1
Cite as drinking water systems, O. Reg. 170/03, Schedule 1 · current to November 11, 2026 · consolidated from April 11, 2022 · read from e-Laws on November 16, 2026
The text
SCHEDULE 1 TREATMENT EQUIPMENT
Municipal: Large Residential Small Residential
Application
1-1. This Schedule applies to the following drinking water systems:
1. Large municipal residential systems.
2. Small municipal residential systems.
General obligations
1-2. (1) The owner of a drinking water system shall ensure the following:
1. Any well that serves as an entry point of raw water supply is constructed and maintained to prevent surface water and other foreign materials from entering the well.
2. Water treatment equipment is provided in accordance with sections 1-3 to 1-5.
(2) The owner of a drinking water system and the operating authority for the system shall ensure the following:
1. The water treatment equipment is in operation whenever water is being supplied.
2. The water treatment equipment is operated in accordance with the Ministry’s Procedure for Disinfection of Drinking Water in Ontario.
3. The water treatment equipment required by section 1-3 or 1-4 is operated in a manner that achieves the design capabilities it is required to have under that section.
4. If the drinking water system’s water treatment equipment provides chlorination or chloramination for secondary disinfection, the equipment is operated so that, at all times and at all locations within the distribution system,
i. the free chlorine residual is never less than 0.05 milligrams per litre, if the drinking water system provides chlorination and does not provide chloramination, or
ii. the combined chlorine residual is never less than 0.25 milligrams per litre, if the drinking water system provides chloramination.
5. Adjustments to the water treatment equipment are carried out only by certified operators or emergency substitute operators.
Primary disinfection for ground water raw water supply
1-3. The owner of a drinking water system that obtains water from a raw water supply that is ground water shall ensure provision of water treatment equipment that is designed to be capable of achieving, at all times, primary disinfection in accordance with the Ministry’s Procedure for Disinfection of Drinking Water in Ontario, including at least 99 per cent removal or inactivation of viruses by the time,
(a) water leaves the point of entry treatment units, in the case of a drinking water system to which, pursuant to section 3-1.1 of Schedule 3, section 1-5 does not apply; or
(b) water enters the distribution system, in any other case.
Filtration and primary disinfection for surface water raw water supply
1-4. The owner of a drinking water system that obtains water from a raw water supply that is surface water shall ensure provision of,
(a) water treatment equipment that,
(i) is designed to be capable of chemically assisted filtration, and
(ii) is designed to be capable of achieving, at all times, primary disinfection in accordance with the Ministry’s Procedure for Disinfection of Drinking Water in Ontario, including at least 99 per cent removal or inactivation of Cryptosporidium oocysts, at least 99.9 per cent removal or inactivation of Giardia cysts and at least 99.99 per cent removal or inactivation of viruses by the time,
(A) water leaves the point of entry treatment units, in the case of a drinking water system to which, pursuant to section 3-1.1 of Schedule 3, section 1-5 does not apply, or
(B) water enters the distribution system, in any other case; or
(b) other water treatment equipment that, in the Director’s opinion, is designed to be capable of producing water of equal or better quality than the equipment described in clause (a).
Secondary disinfection
1-5. The owner of a drinking water system shall ensure provision of,
(a) water treatment equipment that is designed to be capable of secondary disinfection using chlorination or chloramination in accordance with the Ministry’s Procedure for Disinfection of Drinking Water in Ontario and that is designed to be capable of achieving, at all locations within the distribution system,
(i) a free chlorine residual of 0.2 milligrams per litre, if the drinking water system provides chlorination and does not provide chloramination, or
(ii) a combined chlorine residual of 1.0 milligrams per litre, if the drinking water system provides chloramination; or
(b) other water treatment equipment that, in the Director’s opinion, is designed to be capable of providing secondary disinfection that is equivalent to or better than the secondary disinfection provided by the equipment described in clause (a).
Primary disinfection equipment that does not use chlorination or chloramination
1-6. (1) If primary disinfection equipment that does not use chlorination or chloramination is provided by a drinking water system, the owner of the system and the operating authority for the system shall ensure that the disinfection equipment is designed and operated in accordance with the standards described in subsection (2), or that,
(a) the disinfection equipment has a feature that ensures that no water is directed to users of water treated by the equipment in the event that the equipment malfunctions, loses power or ceases to provide the appropriate level of disinfection; and
(b) if the disinfection equipment malfunctions, loses power or ceases to provide the appropriate level of disinfection, a certified operator or emergency substitute operator takes appropriate action at the location where the equipment is installed before water is again directed to users of water treated by the equipment.
(2) The standards referred to in subsection (1) are the following:
1. The disinfection equipment must have a feature that causes an alarm to signal immediately in the following locations if the disinfection equipment malfunctions, loses power or ceases to provide the appropriate level of disinfection:
i. The building or structure where the disinfection equipment is installed.
ii. A location where a person is present, if a person is not always present at the building or structure where the disinfection equipment is installed.
2. If an alarm signals under paragraph 1, a certified operator or emergency substitute operator who is at the building or structure where the disinfection equipment is installed must take appropriate action or, if no certified operator or emergency substitute operator is at that location, a certified operator or emergency substitute operator must promptly be dispatched to that location to take appropriate action.
3. A certified operator or emergency substitute operator who is dispatched under paragraph 2 must arrive at the building or structure where the disinfection equipment is installed as soon as possible.
(3) If primary disinfection equipment that does not use chlorination or chloramination is provided by a large municipal residential system, the owner of the system and the operating authority for the system shall ensure that the disinfection equipment has a recording device that continuously records the performance of the disinfection equipment.
OWRA approvals and OWRA orders with less stringent requirements
1-7. This Schedule prevails over an OWRA approval or OWRA order granted or issued before August 1, 2000 that provides for less stringent requirements.
OWRA approvals that give additional time for compliance
1-8. If an OWRA approval granted on or after August 1, 2000 provides that a drinking water system is required, by a date specified in the approval that is later than the date this Regulation comes into force,
(a) to comply with section 5 of Ontario Regulation 459/00 (Drinking Water Protection — Larger Water Works); or
(b) to ensure that water treatment equipment is provided for primary disinfection, secondary disinfection or filtration,
sections 1-3 to 1-6 do not apply until the date specified in the approval.
1-9. Revoked: O. Reg. 253/05, s. 11.
Read the drinking water systems on e-Laws ↗
Made under Safe Drinking Water Act, 2002, S.O. 2002, c. 32.