drinking water systems, O. Reg. 170/03
Schedule 13
Cite as drinking water systems, O. Reg. 170/03, Schedule 13 · current to November 11, 2026 · consolidated from April 11, 2022 · read from e-Laws on November 16, 2026
The text
SCHEDULE 13 CHEMICAL SAMPLING AND TESTING
Municipal: Large Residential Small Residential
Non-Municipal: Year-Round Residential
Application
13-1. This Schedule applies to the following drinking water systems:
1. Large municipal residential systems.
2. Small municipal residential systems.
3. Revoked: O. Reg. 247/06, s. 24 (1).
4. Non-municipal year-round residential systems.
5. Revoked: O. Reg. 247/06, s. 24 (2).
Inorganics
13-2. (1) The owner of a large municipal residential system and the operating authority for the system shall ensure that,
(a) at least one water sample is taken every 12 months, if the system obtains water from a raw water supply that is surface water; or
(b) at least one water sample is taken every 36 months, if the system obtains water from a raw water supply that is ground water.
(2) The owner of a large municipal residential system and the operating authority for the system shall ensure that each of the samples taken under subsection (1) is tested for every parameter set out in Schedule 23.
(3) The owner of a small municipal residential system or non-municipal year-round residential system and the operating authority for the system shall ensure that at least one water sample is taken every 60 months and tested for every parameter set out in Schedule 23.
13-3. Revoked: O. Reg. 399/07, s. 6 (1).
Organics
13-4. (1) The owner of a large municipal residential system and the operating authority for the system shall ensure that,
(a) at least one water sample is taken every 12 months, if the system obtains water from a raw water supply that is surface water; or
(b) at least one water sample is taken every 36 months, if the system obtains water from a raw water supply that is ground water.
(2) The owner of a large municipal residential system and the operating authority for the system shall ensure that each of the samples taken under subsection (1) is tested for every parameter set out in Schedule 24.
(3) The owner of a small municipal residential system or non-municipal year-round residential system and the operating authority for the system shall ensure that at least one water sample is taken every 60 months and tested for every parameter set out in Schedule 24.
Increased frequency under ss. 13-2 and 13-4
13-5. (1) If a test result obtained under section 13-2 or 13-4 for a parameter exceeds half of the standard prescribed for the parameter in Schedule 2 to the Ontario Drinking Water Quality Standards, the frequency of sampling and testing for that parameter under that section shall be increased so that at least one water sample is taken and tested every three months.
(2) Subsection (1) ceases to apply to a parameter if,
(a) in the case of a drinking water system that obtains water from a raw water supply that is surface water, for four consecutive three-month periods in which the system is in operation, none of the test results obtained under section 13-2 or 13-4 for the parameter exceed half of the standard prescribed for the parameter in Schedule 2 to the Ontario Drinking Water Quality Standards; or
(b) in the case of a drinking water system that obtains water from a raw water supply that is ground water, for two consecutive three-month periods in which the system is in operation, none of the test results obtained under section 13-2 or 13-4 for the parameter exceed half of the standard prescribed for the parameter in Schedule 2 to the Ontario Drinking Water Quality Standards.
Trihalomethanes
13-6. (1) The owner of a drinking water system that provides chlorination or chloramination and the operating authority for the system shall ensure that at least one distribution sample is taken in each calendar quarter, from a point in the drinking water system’s distribution system, or plumbing that is connected to the drinking water system, that is likely to have an elevated potential for the formation of trihalomethanes.
(2) The owner of the drinking water system and the operating authority for the system shall ensure that each of the samples taken under subsection (1) is tested for trihalomethanes.
(3) For the purposes of Schedule 2 to the Ontario Drinking Water Quality Standards, the running annual average of quarterly results with respect to trihalomethanes shall be calculated for each calendar quarter by using the following formula:
[A + B + C + D] ÷ 4
in which,
“A” is the average of all the results from the samples tested under subsection (2) in that calendar quarter,
“B” is the average of all the results from the samples tested under subsection (2) in the most recent calendar quarter preceding the calendar quarter referred to in “A” in which testing was carried out,
“C” is the average of all the results from the samples tested under subsection (2) in the most recent calendar quarter preceding the calendar quarter referred to in “B” in which testing was carried out, and
“D” is the average of all the results from the samples tested under subsection (2) in the most recent calendar quarter preceding the calendar quarter referred to in “C” in which testing was carried out.
(4) Despite subsection (1) and subject to subsections (5) and (6), if the following conditions have been met after samples have been taken and tested under subsections (1) and (2) in at least 12 consecutive calendar quarters, a drinking water system that is a small municipal residential system or a non-municipal year-round residential system may cease sampling and testing for eight consecutive calendar quarters:
1. No single test result obtained in the previous 12 consecutive calendar quarters indicated that the concentration of trihalomethanes was greater than 0.050 milligrams per litre.
2. The drinking water system’s raw water supply is the same source of raw water supply that was used in the calendar quarters referred to in paragraph 1.
3. No alterations that may increase levels of trihalomethanes in the drinking water system have been made to the treatment equipment used in the calendar quarters referred to in paragraph 1.
4. The owner or operating authority of the drinking water system did not receive a written direction described in subsection (6) from the Director during the calendar quarters referred to in paragraph 1.
(5) Subject to subsection (6), a drinking water system that is a small municipal residential system or a non-municipal year round residential system referred to in subsection (4) that ceases to sample and test for eight consecutive calendar quarters shall resume the sampling and testing required under subsections (1) and (2) for four consecutive calendar quarters and may continue to cease sampling and testing for eight consecutive calendar quarters and resume sampling and testing for four consecutive calendar quarters for as long as the following conditions are met with respect to the period of sampling and testing:
1. No single test result obtained in the four consecutive calendar quarters period of sampling and testing indicated that the concentration of trihalomethanes was greater than 0.050 milligrams per litre.
2. The drinking water system’s raw water supply is the same source of raw water supply that was used in the calendar quarters referred to in paragraph 1 as well as in the eight consecutive calendar quarters that immediately preceded the sampling and testing period.
3. No alterations that may increase levels of trihalomethanes in the drinking water system have been made to the treatment equipment used in the calendar quarters referred to in paragraph 1 as well as in the eight consecutive calendar quarters that immediately preceded the sampling and testing period.
4. The owner or operating authority of the drinking water system did not receive a written direction described in subsection (6) from the Director during the calendar quarters referred to in paragraph 1 or during the eight consecutive calendar quarters that immediately preceded the sampling and testing period.
(6) Despite subsections (4) and (5), if the Director has knowledge of water chemistry changes in the water of a drinking water system or alterations to the treatment equipment and in the Director’s opinion the changes or alterations may increase levels of trihalomethanes in the drinking water system, the Director shall provide a written direction to the owner or operating authority of the drinking water system that the requirements in subsections (1) and (2) to sample and test in each calendar quarter apply to the system.
Haloacetic acids
13-6.1 (1) The owner of a drinking water system that provides chlorination or chloramination and the operating authority for the system shall ensure that at least one distribution sample is taken in each calendar quarter, from a point in the drinking water system’s distribution system, or plumbing that is connected to the drinking water system, that is likely to have an elevated potential for the formation of haloacetic acids.
(2) The owner of the drinking water system and the operating authority for the system shall ensure that each of the samples taken under subsection (1) is tested for haloacetic acids.
(3) For the purposes of Schedule 2 to the Ontario Drinking Water Quality Standards, the running annual average of quarterly results with respect to haloacetic acids shall be calculated for each calendar quarter by using the following formula:
[A + B + C + D] ÷ 4
in which,
“A” is the average of all the results from the samples tested under subsection (2) in that calendar quarter,
“B” is the average of all the results from the samples tested under subsection (2) in the most recent calendar quarter preceding the calendar quarter referred to in “A” in which testing was carried out,
“C” is the average of all the results from the samples tested under subsection (2) in the most recent calendar quarter preceding the calendar quarter referred to in “B” in which testing was carried out, and
“D” is the average of all the results from the samples tested under subsection (2) in the most recent calendar quarter preceding the calendar quarter referred to in “C” in which testing was carried out.
(4) Despite subsection (1) and subject to subsection (5), if the following conditions have been met after samples have been taken and tested under subsections (1) and (2) in at least 12 consecutive calendar quarters, a drinking water system that is a small municipal residential system or a non-municipal year-round residential system may cease sampling and testing for eight consecutive calendar quarters:
1. No single test result obtained in the previous 12 consecutive calendar quarters indicated that the concentration of haloacetic acids was greater than 0.040 milligrams per litre.
2. The drinking water system’s raw water supply is the same source of raw water supply that was used in the calendar quarters referred to in paragraph 1.
3. No alterations that may increase levels of haloacetic acids in the drinking water system have been made to the treatment equipment used in the calendar quarters referred to in paragraph 1.
4. The owner or operating authority of the drinking water system did not receive a written direction described in subsection (6) from the Director during the calendar quarters referred to in paragraph 1.
(5) A drinking water system that is a small municipal residential system or a non-municipal year round residential system referred to in subsection (4) that ceases to sample and test for eight consecutive calendar quarters shall resume the sampling and testing required under subsections (1) and (2) for four consecutive calendar quarters and may continue to cease sampling and testing for eight consecutive calendar quarters and resume sampling and testing for four consecutive calendar quarters for as long as the following conditions are met with respect to the period of sampling and testing:
1. No single test result obtained in the four consecutive calendar quarters period of sampling and testing indicated that the concentration of haloacetic acids was greater than 0.040 milligrams per litre.
2. The drinking water system’s raw water supply is the same source of raw water supply that was used in the calendar quarters referred to in paragraph 1 as well as in the eight consecutive calendar quarters that immediately preceded the sampling and testing period.
3. No alterations that may increase levels of haloacetic acids in the drinking water system have been made to the treatment equipment used in the calendar quarters referred to in paragraph 1 as well as in the eight consecutive calendar quarters that immediately preceded the sampling and testing period.
4. The owner or operating authority of the drinking water system did not receive a written direction described in subsection (6) from the Director during the calendar quarters referred to in paragraph 1 or during the eight consecutive calendar quarters that immediately preceded the sampling and testing period.
(6) Despite subsections (4) and (5), if the Director has knowledge of water chemistry changes in the water of a drinking water system or alterations to the treatment equipment and in the Director’s opinion the changes or alterations may increase levels of haloacetic acids in the drinking water system, the Director shall provide a written direction to the owner or operating authority of the drinking water system that the requirements in subsections (1) and (2) to sample and test in each calendar quarter apply to the system.
Nitrate and nitrite
13-7. The owner of a drinking water system and the operating authority for the system shall ensure that at least one water sample is taken every three months and tested for nitrate and nitrite.
Sodium
13-8. The owner of a drinking water system and the operating authority for the system shall ensure that at least one water sample is taken every 60 months and tested for sodium.
Fluoride
13-9. If a drinking water system does not provide fluoridation, the owner of the system and the operating authority for the system shall ensure that a water sample is taken at least once every 60 months and tested for fluoride.
First tests
13-10. Where this Schedule requires that water samples be taken and tested for a parameter with a frequency of a period of time fixed by this Schedule, the owner of the drinking water system and the operating authority for the system shall ensure that the first sample is taken and tested for that parameter,
(a) within that period of time after the latest of,
(i) the date the last sample was taken and tested for that parameter under Ontario Regulation 459/00 (Drinking Water Protection — Larger Water Works) or Ontario Regulation 505/01 (Drinking Water Protection — Smaller Water Works Serving Designated Facilities), if one of those regulations applied to the drinking water system,
(ii) the date the last sample was taken and tested for that parameter for the purpose of preparing a report under section 13 of Ontario Regulation 459/00, if that regulation applied to the drinking water system, and
(iii) the date the last sample was taken and tested for that parameter before this Regulation came into force for the purpose of complying with an OWRA approval or OWRA order or making an application for an OWRA approval, if a sample was taken and tested for that parameter for that purpose before this Regulation came into force; or
(b) within that period of time or 12 months, whichever is shorter, after this Schedule begins to apply to the drinking water system, if clause (a) does not apply.
60-day shutdowns, etc.
13-11. Sampling and testing is not required under sections 13-5, 13-6, 13-6.1 and 13-7 during a period of 60 or more consecutive days when,
(a) the drinking water system is not in operation; or
(b) the drinking water system supplies water only to five or fewer private residences, and all private residences are occupied by the owner of the system, members of the family of the owner of the system, employees or agents of the owner of the system, or members of the families of employees or agents of the owner of the system.
13-12. Revoked: O. Reg. 249/03, s. 18.
Read the drinking water systems on e-Laws ↗
Made under Safe Drinking Water Act, 2002, S.O. 2002, c. 32.